Motor FLA Chart Guide: Find Nameplate FLA and NEC FLC

Look up selected motor FLC values by horsepower, phase, and voltage, then distinguish code-table current from nameplate FLA.

These selected reference rows cover 1–10 HP at the voltages shown. They are code-table FLC values, not readings from your motor nameplate or breaker settings. The two source editions are labeled separately; values have not been verified against the 2026 NEC or your local adoption.

Single-Phase Motor FLC Reference

Selected 2017 NEC Table 430.248 reference values. Current in amperes.
Motor HP115 V FLC (A)230 V FLC (A)
1168
22412
33417
55628
7.58040
1010050

Source: Schneider Electric Digest — Motor Protection Selection Tables (selection tables explicitly based on the 2017 NEC).

Three-Phase Motor FLC Reference

Selected 2023 NEC Table 430.250 reference values for three-phase induction motors with normal torque at usual speeds. Current in amperes; synchronous-motor values are not included.
Motor HP230 V FLC (A)460 V FLC (A)
14.22.1
26.83.4
39.64.8
515.27.6
7.52211
102814

Source: Eaton — 2023 NEC Code Changes, page 39 (Table 430.250, printed page 39).

Coverage map: when the selected rows are enough

The tables above answer a narrow lookup task: the listed horsepower, phase, and voltage combinations from their labeled source editions. Use this checklist before copying a row into a design worksheet.

Route each motor to the evidence that actually matches it.
Your motor dataNext actionWhy the page does not infer it
Listed HP and voltage match a table rowRecord phase, voltage column, table number, source edition, and local adoption.The same HP can have different code paths by phase and motor type.
208 V, 575 V, or another voltage not shownOpen the adopted code table or manufacturer documentation for that voltage.No unlisted voltage is interpolated from the selected rows.
HP, motor type, or phase is not representedIdentify the applicable table and motor construction before looking up current.Tables 430.248, 430.249, and 430.250 have different scopes.
Nameplate gives a rated currentUse the nameplate value with its matching voltage, phase, frequency, and connection.Nameplate FLA and code-table FLC serve different tasks.
Wire, overload, breaker, or disconnect decisionStart a separate conductor/protection calculation using the adopted code and equipment instructions.A current lookup alone does not select a protective device or conductor.

Record these fields before lookup

  • Motor or equipment nameplate current, rated voltage, phase, frequency, and connection.
  • Motor type, horsepower/output, duty, and whether the equipment is a hermetic compressor or packaged appliance.
  • Code edition and jurisdiction, table number, row, voltage column, and the design task (conductor, overload, short-circuit protection, or voltage drop).

Motor FLA vs. NEC FLC

FLA (full-load amps) is the motor's rated current under its stated operating conditions; use the value on the motor or equipment nameplate when you need nameplate current. FLC (full-load current) is also used as a code term. It is not safe to treat the two labels as interchangeable for every motor, calculation, or jurisdiction.

For U.S. installations, NEC Article 430 has distinct rules for motor conductors, branch-circuit short-circuit and ground-fault protection, and overload protection. The applicable path depends on the motor and equipment, exceptions, the locally adopted NEC edition, and the authority having jurisdiction. Confirm the exact rule in the adopted code and manufacturer instructions.

Which NEC motor table should you verify?

The table selection is part of the answer. Confirm the motor type and the edition adopted by the authority having jurisdiction before copying any value from NFPA 70.

ReferenceScope to verifyUse boundary
Table 430.248Single-phase AC motorsVerify the motor type, horsepower, voltage column, edition and any applicable exception in the adopted code.
Table 430.249Two-phase AC motorsDo not substitute a single-phase or three-phase row because the horsepower and voltage look similar.
Table 430.250Three-phase AC motorsVerify the system voltage, frequency, motor type and the locally adopted edition before using a table value for a code calculation.

Worked selection example: A 10 HP, 230 V, three-phase motor points to the three-phase table path, so start at Table 430.250. The table lookup is separate from the nameplate FLA, conductor ampacity, overload setting and short-circuit/ground-fault protection calculation. Record the exact edition, row, voltage column and local adoption before treating the value as a design input.

How to Find the Motor's Rated Current

  1. Read the motor or equipment nameplate for rated current and its matching voltage, phase, frequency, and connection.
  2. Check the manufacturer's installation instructions and equipment markings, especially for HVAC and refrigeration equipment.
  3. If the nameplate does not give the value needed for a code calculation, identify the motor type and use the applicable table and rules in the locally adopted electrical code. Do not infer a design value from horsepower alone.

For a U.S. NEC installation, consult the applicable edition of NFPA 70 and local adoption. The current NFPA publication is NFPA 70 (2026), National Electrical Code; jurisdictions may adopt a different edition or amendments.

FLA, FLC, RLA, and LRA

LabelWhere it is usedHow to treat it
FLAMotor or equipment nameplate / motor dataRated full-load current under the stated conditions; record the matching voltage and phase.
FLCElectrical code calculationsUse the value and calculation path specified by the applicable code for that motor and task.
RLAOften shown for hermetic motor-compressorsUse the equipment documentation; do not assume it equals a general-purpose motor's FLA.
LRAMotor-compressor or motor starting dataStarting / locked-rotor information; it is not the running FLA.

Before Using a Motor Current Value for Design

First identify what you are sizing: a conductor, controller, disconnect, branch-circuit short-circuit and ground-fault protective device, overload device, or a voltage-drop estimate. These are separate tasks and may use different nameplate, code-table, equipment-marking, and installation inputs.

Confirm motor type, horsepower or output, rated voltage, phase, frequency, duty, and equipment listing. Then follow the adopted local electrical code and the manufacturer's instructions. A percentage copied from a generic chart is not a universal breaker, fuse, overload, or wire-selection rule.

The lookup above covers only the listed horsepower and voltage rows from its labeled sources. It does not determine wire size, overload settings, or branch-circuit protection.

Use the Current Estimator for a Planning Estimate

The linked calculator estimates operating current from entered power, voltage, phase, efficiency, and power factor, then applies a selectable rough starting-current factor. The result is a model estimate, not a motor-nameplate reading, code-table lookup, or NEC compliance check. Use manufacturer data and the applicable code for installation decisions.

Open the Motor Current Estimator →

Worked planning example

For a 5 kW, 400 V, three-phase motor with 90% efficiency and 0.85 power factor, the simplified running-current estimate is I = P ÷ (√3 × V × η × PF) = 5,000 ÷ (1.732 × 400 × 0.90 × 0.85) ≈ 9.4 A. This is a planning estimate only; nameplate current, starting behavior, conductor sizing, overloads, and overcurrent protection still require the equipment data and adopted code.

Source and Applicability

For U.S. work, use the NFPA 70 publication for the relevant edition, verify which edition and amendments the local jurisdiction has adopted, and consult the authority having jurisdiction when needed. Other countries and regions use different electrical rules; this page does not certify compliance outside the adopted U.S. NEC path.

Reviewed 2026-10-10. The selected rows above retain their source editions: Schneider Electric’s 2017 NEC reference for single-phase motors and Eaton’s 2023 NEC reference for three-phase motors. No 208 V values or unlisted rows are inferred.

Frequently Asked Questions

Where can I find a motor's FLA?

Check the motor or equipment nameplate and the manufacturer's data for the rated voltage and phase. If you need a code-table value for an installation calculation, follow the locally adopted code path for that motor.

Can I use this page to choose a wire or breaker?

No. The selected reference values identify code-table motor current only. Wire, breaker, and overload selection require separate rules, equipment data, and the locally adopted code.

Is the calculator result the motor's actual FLA?

No. It estimates current from the inputs and assumptions shown. Use the nameplate or manufacturer data for the motor's rated current.