Project inputs
Formula reference
Available pressure = blower allowance − Σ external losses
Friction rate = available pressure × 100 ÷ TEL (IP); available pressure ÷ TEL (SI)
Use the result as a design input
This worksheet turns the equipment and route data you provide into one pressure budget for the controlling supply/return circuit. It does not supply manufacturer coil, filter, grille, terminal, or fitting losses; enter the values at the design airflow and maintenance condition.
- Read the blower's external-static allowance and identify its test boundary.
- Subtract only external component losses that are outside that boundary.
- Add straight and fitting equivalent lengths for the critical supply and return circuit.
- Use the resulting friction rate to select each duct section, then recompute actual losses and verify velocity, noise, balancing, and fan selection.
Boundaries
A zero or negative available pressure means the stated components consume the entire allowance. Review the boundary, component selection, route, or equipment before sizing duct. Parallel branches are not added to the controlling TEL.
FAQ
What does this static pressure calculator calculate?
It subtracts external component losses from the blower's stated external-static allowance, adds supply and return equivalent lengths, and divides the remaining pressure by the complete circuit length to show a friction rate.
What is total equivalent length (TEL)?
TEL is the controlling supply and return route length after straight duct and fitting equivalent lengths are accounted for. Do not add parallel branches to the critical circuit.
Can this calculator select a fan or duct size?
No. It is a pressure-budget worksheet. Use the equipment fan table and manufacturer component curves, then verify each duct section, fitting, velocity, balancing condition, and the final fan selection.
Sources and next steps
- Duct static pressure: equal friction vs equal velocity
- Duct sizing calculator
- Return grille sizing and pressure loss
- ACCA: what friction rate means
The numeric example values are editable teaching inputs. Equipment and fitting manufacturer data control the final design.